GOT SIMPLE Series

HomeGOT SIMPLE Series

Quick Inquiry

    GOT SIMPLE Series

    GS21-N Model

    The GOT SIMPLE Series upgrade brings the most demanded new features

    – Support RS-485 connection
    – Support outline font
    – Operation log function
    – VNC server function
    – User memory capacity (9 MB → 15 MB)

    GOT SIMPLE Series

    General specifications

    ItemSpecifications
    Operating ambient temperature *10 to 50 ℃
    Storage ambient temperature-20 to 60 ℃
    Operating/Storage ambient humidity10 to 90% RH, non-condensing *2 (The wet bulb temperature is 39℃).
    Vibration resistanceConforms to
    IEC 61131-2
    FrequencyAccelerationHalf-amplitudeSweep Count
    Under intermittent vibration5 to 8.4 Hz3.5 mm10 times each
    in X, Y and Z
    directions
    8.4 to 150 Hz9.8 m/s²
    Under continuous vibration5 to 8.4 Hz1.75 mm
    8.4 to 150 Hz4.9 m/s²
    Shock resistanceConforms to IEC 61131-2 (147m/s², 3 times each in the X, Y, and Z directions)
    Operating atmosphereMust be free of lamp black, corrosive gas, flammable gas, or excessive amount of electro conductive dust particles. Must be no direct sunlight. (Same as for saving)
    Operating altitude *32000m (6562ft) max.
    Installation locationInside control panel
    Overvoltage category *4Ⅱ or less
    Pollution degree *52 or less
    Cooling methodSelf-cooling
    GroundingGrounding with a ground resistance of 100 Ω or less by using a ground cable that has a cross-sectional area of 0.14 to 1.5 mm2 (solid wire), 0.14 to 1.0 mm2 (stranded wire), or 0.25 to 0.5 mm2 (rod terminal with an insulation sleeve). If impossible, connect the ground cable to the control panel.
    • *1 Includes the temperature inside the enclosure of the control panel to which the GOT is installed.
    • *2 If the ambient temperature exceeds 40 °C, the absolute humidity must not exceed 90% RH at 40 °C.
    • *3 Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0 m (0 ft).
      Failure to observe this instruction may cause a malfunction. When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result, the touch panel may be difficult to press, and the sheet may be peeled off.
    • *4 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises.
      Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V.
    • *5 This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used.
      In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.